AITHA AITHA
Client login
ES EN
Talk to the team

#Datasheet

Operate unattended infrastructure with each action authenticated and logged

Inputs and outputs, communications, authenticated intervention and local logging during network outages. Reports to AITHANEX or to your own remote control system.

Technology core

AURA X36 integrates AITHA Core on its own PCB. The Core datasheet details the shared firmware, communications and power.

Technical capabilities

AreaScope
SignalsReading of states, sensors and variables defined by engineering.
Inputs and outputsMonitoring of digital and analog inputs, current measurement and control through dry-contact relays.
SecurityMonitoring of access, intrusion, tampering or other site events.
Local loggingKeeps events through connectivity interruptions.
ConnectivityRS485, RS232, USB, Ethernet, Wi-Fi, Bluetooth, 4G IoT.
ProtocolsMQTT with AITHANEX and buses documented for the deployment.
Remote operationMonitoring, alerts, actuation rules and remote update.

System functionality

FunctionDescription
Remote monitoringCentralises acquisition of digital states, analog signals and current variables from sensors, technical contacts, loops and auxiliary elements.
Control of external elementsRelay outputs can drive external devices, automation, signals or subsystems associated with the monitored infrastructure.
Communication with AITHANEXMQTT over the link available at each site (Ethernet, Wi-Fi or 4G IoT). Events are published to the defined topics and downstream commands are received by subscription.
Identification and traceabilityThe mobile app allows local connection, authorized-user identification and logging of the action performed; the information is stored locally and synchronized with AITHANEX.

Inputs and outputs

TypeQuantitySpecification
Digital inputs16Optocoupled.
Digital outputs (relays)8Potential-free. 10 A up to 250 Vac.
Analog voltage inputs30–10 V.
Analog voltage output10–10 V.
Analog current inputs20–20 mA. Loop measurement up to 1000 m.
Authentication interface1 input + 1 outputNon-programmable. Dedicated.
Safety cable input sensor1Dedicated.

Device communications

InterfaceQuantity / SpecificationAvailability
RS485 (standard)1 port, two wires.Standard
RS485 reinforced (EMC)1 port, higher EMC requirement.Standard
RS2321 port.Standard
USB1 service port.Standard
Ethernet—Standard
Wi-Fi—Standard
Bluetooth—Standard
4G IoTMulti-frequency module, global coverage.Standard
MQTT to AITHANEXOver Ethernet, Wi-Fi or 4G.Standard
OTARemote firmware update.Standard

Construction and operating environment

ParameterValueNotes
Cabinet materialAluminum with thermal dissipation.Screw closure.
Dimensions320 × 220 × 100 mm—
MountingWall, DIN rail or technical cabinet.—
Operating temperature-20 to +60 °C—
Environmental protectionIP20Not sealed for direct outdoor exposure.
Power Supply100–240 Vac, 50/60 Hz—
Board treatmentTropicalization—
Visual indicatorsStatus LED—
Integrated IMUAccelerometer and gyroscope—

Authenticated intervention

Procedure

  • 1. Operator identification in a secure app.
  • 2. Local connection via Bluetooth.
  • 3. Authorized temporary security deactivation.
  • 4. Photographic evidence captured from the app.
  • 5. Log of time, equipment, action and result.

Logging and monitoring

Local logging

  • Events, access and operations.
  • Retains data during connectivity interruptions.

Server logging

  • Via MQTT with AITHANEX.
  • Access and intervention traceability.

Typical applications

Typical sites
Telecom shelters and cabinets
Prefabricated installations and remote sites
Energy infrastructure
Technical rooms
Distributed industrial installations

Known limits

Not suitable for direct outdoor exposure

  • IP20: the cabinet is not sealed.
  • Requires installation in a technical cabinet or protected enclosure.

Non-programmable authentication interface

  • The authentication input and output are dedicated and not reassignable.
  • Cannot be used as general-purpose I/O.

AC-only power supply

  • The unit operates on 100–240 Vac.
  • Does not accept direct DC power without an external adapter.

Firmware from the Core

  • LTE, GNSS and BLE specifications follow the installed AITHA Core version.
  • Check the Core technical datasheet for available hardware variants.

Documentation in PDF

Download the product document.

Validate the integration in your installation

Review with the technical team inputs, outputs, protocols and system architecture.

Contact